Desktop|中文
Home About Us Products + News Center Technical Articles Messages Contact Us

Product Details

全自动Dielectric Loss Tester-扬州达瑞

JYV-B SF6 Gas Vacuum Pumping and Filling Device - Yangzhou Darui

Published: 2024-06-30 13:02:24

Views: 2922

Category: SF6 Vacuuming & Recovery

Product Description


JYV-B SF6 Gas Vacuum Pumping and Filling Device 

Darui Electric recommends:


Main configuration of JYV-B SF6 gas vacuum pumping and filling device:



1. SF6 compressor requirements: CA-0300 hermetic compressor



a: Theoretical displacement: 12m3/h



b: Maximum discharge pressure: 2.5Mpa



c: Minimum suction pressure: 50Kpa



d: Maximum suction pressure: 0.35~0.8 Mpa



e: Power: 2.2KW



f: Power supply: 380V 50HZ



2. Vacuum pump: two-stage rotary vane vacuum pump



a: Water-cooled vacuum pump



b: Vacuum pumping rate 4L/s



JYV-B SF6 gas vacuum pumping and filling device device functions



1. Measure the vacuum degree of the device itself, electrical equipment, storage tanks, and vacuum pumping



2. Recover gas from electrical equipment



3. Dry and purify the recovered and refilled SF6 gas



4. Fill SF6 electrical equipment with gas



5. Compress and liquefy SF6 gas in electrical equipment for storage



Process description:



 1. SF6 gas recovery



When SF6 is extracted from a gas chamber, the gas automatically flows through the purification filter, is compressed and cooled by the SF6 compressor, and can be stored in the SF6 storage tank in gaseous form or in liquid form at a certain high pressure.



2. Vacuum pumping of SF6 switch



The air and moisture in the switch can be removed by the vacuum pump, and the outlet of the vacuum pump is connected to the atmosphere.



3. Gas filling



The purified and dried SF6 is filled back from the storage tank into the evacuated gas chamber until the pressure in the chamber reaches the set working pressure. The above work is carried out in two steps:



Use the pressure of the SF6 storage tank to make the gas flow to the SF6 switch until the preset filling pressure is reached.



2. When the pressure of the SF6 storage tank is balanced with the pressure of the SF6 switch, use the compressor to pressurize and fill until the preset filling pressure is reached.



Technical conditions



1. Type: mobile, air-cooled



2. Working principle



1) Use the compressor to condense and liquefy SF6 gas at high pressure.



2) Heat exchanger assists gas recovery and refilling



3) Gas is filled through a buffer during filling



3. Main performance and technical parameters



1) Ultimate vacuum of the device ≤133Pa (special requirements can be ≤5Pa)



2) Vacuum pumping rate of the device 55m³/h



3) Initial filling pressure of the device <133Pa (user-defined as required)





Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.

WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us