Technical Parameters of GIS Vacuum Pump Gas Evacuation and Filling Device
- Can quickly evacuate SF6 electrical equipment, with good sealing performance
- Can quickly fill SF6 electrical equipment, with high efficiency
- Flexible filling methods, adjustable pressure for filling
- Customized phase sequence protection device, withstanding voltage up to 500V, greatly improving reliability
- Adopts air cooling and mobile design, can be used without water source.
- Three-phase five-wire power supply, equipped with leakage protector for the whole machine
- Hand-push mobile structure, compact and sturdy, adaptable to various harsh environments
- The ball valve adopts the working principle of American Swagelok, with automatic compensation performance of sealing elements.
- The ball valve is applied in vacuum and pressure conditions, ensuring no leakage in both vacuum and pressure states
- High-quality casters for easy movement without damaging the floor.
- The whole machine has complete functions, small size, light weight, low energy consumption, and low noise
- Adopts pointer-type vacuum gauge, with stable performance, easy reading of vacuum degree, and accurate measurement
- Fully automatic anti-oil return system
- Performance can be comparable to well-known foreign brands
- Can be customized with one vacuum pump to evacuate 3 chambers simultaneously, flexible movement, easy operation, and good sealing
- Can be used for SF6 dew point, purity, decomposition products, as well as leak detection and annual leak rate testing functions
- Technical Parameters:
Type
Hand-push mobile type
Rotary vane vacuum pump brand
2xz-15B
Cooling method
Vacuum pump adopts air cooling, can run for long periods
Mobility type
Manual movement (lightweight)
Working principle
High-pressure ball valve, vacuum gauge assists vacuum pump for evacuation
Pumping speed (m³/h)
55
Ultimate vacuum of equipment (absolute pressure Pa)
10
Initial pressure for evacuation
53kPa
Final pressure for evacuation
30 Pa
Refilling rate
5m/h
Vacuum measurement method
Pointer-type vacuum gauge
Vacuum gauge measurement range
0-10³ Pa
Annual leak rate
≤1%
Working environment temperature
Upper limit: +40℃ Lower limit: +5℃, -10℃, -30℃
Noise
≤60dB sound pressure level
Power supply
AC three-phase / four-core 380V +10%, 50Hz
Power (KW)
1.5
SF6 special ball valve
High-pressure vacuum dual-purpose ball valve (13.5MPa, no leakage)
Evacuation interface
M27×1.5, three-way optional
Factory-equipped steel wire braided rubber hose
M27×1.5×10 meters, one piece
Weight (Kg)
66