Load Bank
Load Bank (also known as "LOADBANK") is a power detection device mainly used for load testing and maintenance of generators, uninterruptible power supplies (UPS), and power transmission equipment. It is a periodic testing and maintenance tool for generator sets and UPS uninterruptible power supplies.
Load Bank Parameters
1. Rated input voltage: Single phase 220V
2. Rated input power: 10KW
3. Power grading: 100W/200W/200W/500W/1KW/2KW/2KW/5KW (customizable according to customer requirements)
4. Power factor: PF=1
5. Load accuracy: ±5%
6. Display mode: Real-time display with voltage and current meters (optional)
7. Working power: Single phase AC220V/50HZ
8. Control mode: Panel manual control, segmented manual adjustment.
9. Insulation class: Class F
10. Protection level: IP20 (suitable for indoor use)
11. Fan noise: 65 decibels
12. Cooling method: Forced air cooling: side air intake, side air exhaust
13. Working mode: Continuous operation
14. Protection functions: Over-temperature alarm, over-temperature protection, buzzer alert, over-current protection, etc.
15. External dimensions: Main unit: width 450 * depth 570 * height 770mm
16. Applicable ambient temperature: -10℃~+50℃
17. Mobility: Equipped with heavy-duty universal casters, 2 at the front and 2 at the rear
18. Applicable relative humidity: ≤95%
19. Altitude: ≤2500 meters