Product Use of Transformer Oil Vacuum Oil Filter:
1. Suitable for on-site maintenance of transformers in large substations above 110KV, and deep purification treatment of new oil, imported oil, mutual inductor oil, ultra-high voltage transformer oil and other oils.
2. Used for maintenance and safe use of power systems and substations in power plants, power stations, power companies, substation industries, metallurgy, petrochemical, machinery, transportation, railway and other industries. It can also be used for vacuum oil filling, vacuum drying, and hot oil circulation of transformers.
3. This series of models has more advantages when used in high-altitude areas.
Product Technical Features:
1. Double-stage high vacuum, large pumping speed, three-dimensional flash evaporation technology for dehydration and degassing, can quickly and efficiently remove moisture, impurities, hydrocarbons and other effective components in oil.
2. Efficiently improve the flash point and dielectric strength of insulating oil.
3. Can meet the requirements of vacuum pumping and vacuum oil filling for transformer body during installation or maintenance on site.
4. Multi-stage precision filtration with gradual densification can effectively remove mechanical impurities in oil.
5. Automatic constant temperature control, automatic liquid level control, automatic defoaming, automatic pressure protection.
6. Can filter oil online, can run unattended, and the running status is displayed by indicator lights.
7. This machine has humanized design, low noise, easy operation, long maintenance intervals, low energy consumption and saves operating costs.
8. The whole machine is equipped with interlocking safety protection. The oil discharge system, vacuum system and heating system are interlocked to avoid misoperation.
9. Multi-stage precision filtration with gradual densification can block fine impurities, has large dirt holding capacity, can be repeatedly cleaned and used, and will not cause secondary pollution.
10. Adopts photoelectric liquid level control method, with sensitive and accurate control, can even sense foam, and is equipped with ultra-high and ultra-low liquid level protection, absolutely no oil spray phenomenon occurs.
11. The standard configuration of the front-stage pump of this machine adopts original imported vacuum pump (natural cooling method), with fast pumping speed, can quickly obtain high working vacuum.
User Optional Configurations:
1. According to user needs, PLC intelligent control, touch screen operation, and dynamic display can be optionally equipped.
2. Main power components, filter materials, and electrical components can be selected from high-quality imported products to improve the performance of the equipment.
3. Can be equipped with online moisture detector.
4. Optional frequency converter, can choose flow rate according to needs.
5. Optional flow meter with accumulation function.
6. Optional external vacuum system for transformer.
7. The whole machine structure can be made into mobile type, fixed type, trailer type (single axle or double axle).
8. Can be made into fully enclosed type, canopy type, canvas cover type, open type.
9. Equipment color can be arbitrarily selected according to needs.
Technical Parameters:
| Item | Parameter Name | Unit | ZYD-30 | ZYD-50 | ZYD-100 | ZYD-150 | ZYD-200 | ZYD-300 | ZYD-500 | |
| Flow Rate | L/H | 1800 | 3000 | 6000 | 9000 | 12000 | 18000 | 30000 | ||
| Working Vacuum Degree | Mpa | -0.08~-0.095 | ||||||||
| Equipment Technical Indicators | Working Pressure | Mpa | ≤0.5 | |||||||
| Constant Temperature Control Range | ℃ | 20~80 | ||||||||
| Power Supply | 380V/50HZ (or according to user needs) | |||||||||
| Working Noise | dB(A) | ≤78 | ||||||||
| Heating Power | KW | 15 | 18 | 30 | 45 | 60 | 75 | 90 | ||
| Total Power | KW | 18 | 21 | 48 | 48 | 65 | 80 | 95 | ||
| Inlet/Outlet Pipe Diameter | mm | 25 | 32 | 40 | 50 | 50 | 65 | 80 | ||
| Equipment Weight | kg | 600 | 800 | 1000 | 1300 | 1800 | 2100 | 2400 | ||
| Length | mm | 1200 | 1250 | 1450 | 1600 | 1600 | 1800 | 1900 | ||
| Overall Dimensions | Width | mm | 1200 | 1250 | 1400 | 1600 | 1600 | 1700 | 1900 | |
| Height | mm | 1700 | 1750 | 1800 | 2100 | 2150 | 2250 | 2300 | ||
| Oil Treatment Indicators | Oil Breakdown Voltage | KV | ≥80(GB/T507) | |||||||
| Water Content in Oil | PPM | ≤1(GB/T7600) | ||||||||
| Gas Content in Oil | % | ≤0.05(GB/T423) | ||||||||
| Filtration Precision | um | ≤1 | ||||||||